Square D’s 40 A, three-pole bolt-on miniature circuit breaker provides circuit protection for compatible power distribution equipment. A Visi-Trip indicator helps identify a tripped breaker, while box lugs accommodate 8–2 AWG copper or aluminium conductors. The standard breaker is HACR rated and occupies three panel spaces.

Key Features

  • 40 A, Three-Pole Protection: Provides a three-pole circuit breaker configuration for applications requiring a 40 A rating.
  • Bolt-On Mounting: Uses a bolt-on connection for installation in compatible equipment.
  • Visi-Trip Indicator: Helps identify when the breaker has tripped.
  • Copper or Aluminium Terminations: Box lugs accommodate conductors from 8 AWG to 2 AWG.
  • Specified Interrupting Ratings: Rated 10 kA at the listed AC voltages and 5 kA at 48 V DC.

Specifications

Product Type Miniature circuit breaker
Range QO
Rated Current 40 A
Number of Poles 3
Mounting Bolt-on
Breaker Type Standard; HACR rated
AC Voltage Rating 240 V AC
AC Interrupting Rating 10 kA at 120 V AC, 120/240 V AC and 240 V AC, 50/60 Hz
DC Interrupting Rating 5 kA at 48 V DC
Electrical Connection Box lugs
Conductor Size 8–2 AWG copper or aluminium
Panel Spaces 3
Trip Indicator Visi-Trip
Ambient Rating 40°C (104°F)
Height × Width × Depth 3.12 × 2.25 × 2.91 in.
Installation Note Verify equipment compatibility, system voltage and required interrupting capacity before installation. Follow manufacturer installation instructions.