The Schneider Electric Thermal Overload Relay (16–24 A) is engineered for reliable motor protection in demanding industrial and commercial applications. Designed to IEC, UL, and CSA standards, this Class 10A relay safeguards motors against overload and phase failure conditions — making it a trusted choice for panel builders, electrical contractors, and maintenance professionals across Canada. With a wide adjustment range of 16–24 A, temperature compensation from -20 to 60 °C, and mercury-free construction, it delivers consistent, code-compliant performance whether mounted under a contactor, on a DIN rail, or on a plate. The red stop and blue reset push-buttons provide intuitive on-site control, while screw clamp terminals ensure fast, secure wiring on the job site.
Specifications
| Thermal Protection Adjustment Range | 16–24 A |
| Current Rating | 24 A |
| Thermal Overload Class | Class 10A IEC 60947-4-1 |
| Rated Operational Voltage | 690 V AC, 0–400 Hz |
| Rated Insulation Voltage | 600 V CSA, 600 V UL, 690 V IEC 60947-4-1 |
| Rated Impulse Withstand Voltage | 6 kV |
| Dielectric Strength | 1.89 kV 50 Hz IEC 60947-1 |
| Network Frequency | 0–400 Hz |
| Tripping Threshold | 1.14 ±0.06 Ir IEC 60947-4-1 |
| Phase Failure Sensitivity | Tripping current 130% of Ir on two phases |
| Conventional Free Air Thermal Current | 5 A signalling circuit |
| Permissible Current | 1.5 A 240 V AC-15 signalling circuit; 0.1 A 250 V DC-13 signalling circuit |
| Control Type | Red push-button stop, Blue push-button reset |
| Connection Type | Screw clamp terminals |
| Screw Clamp Terminal Size | Control circuit: 1–2.5 mm²; Power circuit: 1–10 mm² |
| Tightening Torque | Control circuit: 1.7 N·m; Power circuit: 2.5 N·m |
| Mounting Support | Plate, rail with specific accessories, under contactor |
| IP Degree of Protection | IP20 IEC 60529 |
| Temperature Compensation Range | -20 to 60 °C |
| Ambient Air Temperature for Operation | -20 to 60 °C (-4 to 140 °F) |
| Ambient Air Temperature for Storage | -60 to 70 °C (-76 to 158 °F) |
| Dimensions (H × W × D) | 66 mm × 45 mm × 70 mm (2.60 in × 1.77 in × 2.76 in) |
| Net Weight | 0.124 kg (0.27 lb) |
| Mechanical Robustness | Vibrations 6 Gn IEC 60068-2-6; Shocks 15 Gn 11 ms IEC 60068-2-7 |
| Material | Mercury Free |
| Standards | IEC 60947-4-1, IEC 60947-5-1, UL 60947-4-1, UL 60947-5-1, CSA C22.2 No 60947-4-1, CSA C22.2 No 60947-5-1, GB/T 14048.4, GB/T 14048.5, EN 50495 |
| Product Certifications | IEC, UL, CSA, CCC, EAC, ATEX, Marine, BV, RINA, DNV-GL, LROS, UKCA |
| Country of Origin | France |